Project Background & Challenge
Specializing in Self Cleaning Filter and Liquid Filters for sustainable infrastructure, LEFILTER supplied raw-water intake filtration for a zero-chiller green data center near Oslo, Norway. The facility pumps cold deep-lake water directly through primary titanium heat exchangers for year-round free cooling. Seasonal spring runoff carried pine needles, glacial silt, and organic plankton that threatened to blind the heat exchanger plates.
Solution: Multi-Candle Backwash Self Cleaning FilterTo achieve ultra-fine filtration across high flow rates with minimal pressure drop, LEFILTER engineered a DN400 multi-candle backwash Self Cleaning Filter fitted with 24 slotted wedge-wire filter candles. When differential pressure reaches 0.035 MPa, a rotary distributor arm isolates and backwashes one candle group at a time using filtered system water, ensuring zero interruption to lake-water cooling flow.
Technical Parameters
Application: Green Data Center Lake-Water Free Cooling Intake
Equipment: Multi-Candle Backwash Self Cleaning Filter (DN400)
Filtration Rating: 60 Micron
Design Flow Rate: 1,100 m³/h
Operating Pressure: 0.4 MPa
Control Interface: Profinet / PLC Automated Backwash Sequence
Results & Customer ValueThe system maintained a PUE of 1.12 throughout seasonal lake turbidity spikes while operating completely unmanned via remote SCADA telemetry.