Data Center Cooling Tower Side-Stream Filtration with Self Cleaning Filter in Malaysia

2026-11-28


Project Background & ChallengeAs an industrial filtration manufacturer specializing in Self Cleaning Filter and Liquid Filters, LEFILTER recently engineered a customized side-stream water treatment solution for a Tier-III hyperscale data center in Johor, Malaysia. Operating 24/7 in a tropical climate, the facility relies heavily on evaporative cooling towers to dissipate heat from high-density server racks. However, airborne dust, pollen, and mineral scale rapidly accumulated in the open-loop condenser water, causing severe fouling in plate heat exchangers and driving up chiller power consumption.


Solution: Scraper-Type Self Cleaning FilterTo eliminate manual basket cleaning and prevent unplanned cooling downtime, our engineering team supplied two sets of DN250 motorized scraper Self Cleaning Filter units installed in a side-stream configuration (treating 15% of the main circulation flow). Equipped with a 100-micron precision wedge-wire screen and an automatic differential pressure controller (set at 0.05 MPa), the Self Cleaning Filter continuously scrapes particulate matter off the inner screen wall without interrupting water flow to the chillers.


Technical Parameters

Results & Customer ValueSince commissioning, the cooling water turbidity has remained consistently below 5 NTU, and heat exchanger delta-T efficiency improved by 14%. The automated blowdown cycle takes only 12 seconds with less than 1% water loss, saving the facility over 180 man-hours of maintenance annually.